Notes:
1- 1 HR FIRE/SMOKE STOREFRONT ENTRANCE ASSEMBLY WITH 1 HR FRAME AND 45-MINUTE LABELED TEMPERATE GLASS SIDELIGHTS (DOORS ONLY ARE ALLOWED TO BE LABELED FOR 20-MINUTE FIRE RATING).
2- 1 HR SERVER/STORAGE ROOM (WITH 1 HR DOOR) TO HAVE SEPARATE HVAC SYSTEM AND ELECTRICAL EMERGENCY PUSH OFFS AS REQ'D.
3- ELECTRICAL FLOOR PENETRATIONS MUST BE BY CORE DRILLING ONLY. ANY FLOOR OUTLET TO BE FIRE RATED POKE-THRU TYPE AS REQ'D.
4- SUBJECT TO FIRE MARSHAL AND FIELD INSPECTIONS.
8800 SQ FT CIFO - 4TH FLOOR