Notes:
2192 AC, 2731 SQ FT, SFR / 2 STORY
1/19/2003 12:00:00 AM
2. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
19. BEAMS: INTER. 10"W X 28"D., EXTER. 10"W X 30"D.
23. GARAGE MUST BE A MIN. 18'W X 20'D CLEAR SHEET ROCK TO SHEET ROCK.
49. STRUCTURAL COL'S MUST BE A MIN. OF 4" X 4" WOOD (OR) 3" O.D. STEEL
54. CSST GAS PIPING PROHIBITED IN FRISCO.
63. RECESSED LIGHT FIXTURES MUST BE 2000 IECC CODE COMPLIANT.
67. 12 SEER ALONG WITH R-6 DUCT WORK REQ'D FOR 2000 IECC COMPLIANCE IN NON ENERGY STAR/GREEN BLDG CONSTRUCTION.