Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, TX DEPT. OF HEALTH'S HOSPITAL LICENCING RULES, PERTINENT LEGISLATIONS AND ALL REVIEW COMMENTS.
2- A 3 HR SEPARATION WALL TO BE IN PLACE BETWEEN THE MOB BLDG AND ANY HOSPITAL'S STRUCTURE BEFORE STARTING FINISH-OUT WORK.
3- THE 2 HR RATING PROTECTION OF BLDG STAIR 1005 MUST CONTINUE INTO THE MOB LOBBY UNTIL EXIT DISCHARGE AS PER CODE. WALLS AND FLOOR/CLG ASSEMBLY OF MOB LOBBY AREA (INCLUDING UNSEPARATED SPACES) MUST BE 2 HR THROUGHOUT UNLESS THE MOB LOBBY IS SEPARATED FROM CORRIDOR 1006 BY A 90 MINUTE 2-WAY EXIT DOOR AS PER COMMENTS.
4- PROVIDE 1 HR OCCUPANCY SEPARATION WALL BETWEEN SURGICAL AND BASIC MEDICAL OFFICE AREAS AS REQUIRED.
5- CORRIDORS 1064 & 1071 TO BE 1 HR PROTECTED AS REQ'D FOR EXIT PASSAGEWAYS.
6- SUBMIT MEDICAL PHYSICIST REPORT AS REQ'D FOR ANY SPACE EXPECTED TO CONTAIN X-RAY EQUIPMENT (AS APPLICABLE) PRIOR STARTING ANY RELATED CONSTRUCTION.
7- SUBJECT TO M.E.P. REVIEWS, TDH APPROVALS, FIRE MARSHAL AND FIELD INSPECTIONS.
13,010 SF, CIFO / CENTENNIAL SURGERY CENTER