Notes:
4669 AC, 6059 SQ FT, SFR / 2 STORY
10/27/2003 12:00:00 AM
2. COMPLIANCE WITH THE APRIL 2003 CONTRACTOR GUIDELINE REQ'D
3. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS
9. BEAMS=10"W X 26"D.
35. 2 X 6 PLUMBING (VENT STACK/WASTE)WALLS REQ'D.
38. 1 HOUR FIRE WALL ASSEMBLY REQ'D - SUBMIT DESIGN PRIOR TO WALL CONSTRUCTION.
39. MAX OF 24 SQ FT OF 6" GLASS BLOCK ALLOWED IN 1 HOUR FIRE RATED WALL ASSEMBLY.
40. ON "0" SET-BACK SIDE OF HOUSE NO METERS OR VENTS ARE ALLOWED. GUTTER DOWNSPOUTS MUST DISCHARGE ONTO SAME PROPERTY 5'-0" FROM FOUNDATION.
44. CO DETECTORS REQ'D ON ELECT LEGEND & ELECT PLAN 1/1000 SQ FT & 1 PER FLOOR MIN PLUS (1) ADD'L AT GARAGE ENTRY IN AC AREA.
46. FRONT ENTRY CURB CUT PER ENCLOSED DESIGN SKETCH.
50. CSST GAS PIPING ALLOWED - SEE INFO SKETCH IN LOBBY AND (OR) ORDINANCE(S) 03-07-58 & 03-07-59.
58. 12 SEER ALONG WITH R-6 DUCT WORK REQ'D FOR 2000 IECC COMPLIANCE IN NON ENERGY STAR/GREEN BLDG CONSTRUCTION.
SECOND FLOOR WITH (2) BEDROOM, (2) BATH AND 333 SQARE FEET ATTIC STORAGE ONLY.
INDICATE FP & FF ELEVATIONS ON PERMIT PACK PLOT PLAN PRIOR TO FORM SURVEY.
LIMIT FUTURE DRAWINGS SUBMITTALS TO 24" X 36" SHEETS.