Notes:
1- CONTINGENT UPON COMPLIANCE WITH CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- SPECIFIC MEDICAL PHYSICIST'S INSTRUCTIONS FOR SHIELDING PROTECTION, PERTINENT FACILITY REGULATIONS & NFPA REQUIREMENTS MUST BE FOLLOWED FOR EACH & EVERY IMAGING EQUIPMENT ROOM OR SPACE.
3- WALLS, CLGS & DOORS OF EQUIPMENT ROOM 111 AND SERVER ROOM 103 TO BE 1 HR RATED ASSEMBLIES AS REQ'D.
4- PROVIDE FREESTANDING WALL RECESSED HAND WASHING FIXTURE (WITH "HANDS-FREE" CONTROLS) NEAR THE ENTRANCE TO MRI ROOM AS REQ'D (UNLESS OTHERWISE LEGISLATIVELY PERMITTED).
5- IF BOTTLED WATER COOLER IS PROVIDED, ONLY ONE INSTALLED (STANDARD HEIGHT) DRINK'G FOUNT. SHALL BE ACCEPTABLE IN LIEU OF DUAL HI/LO TYPE.
6- DUE TO TIGHT LAYOUT, PROVIDE AT LEAST ONE OF THE DRESSING ROOMS WITH ADA REQ'D 24" X 48" BENCH. - BOTH DRESSING ROOMS SHALL BE ENTERED THRU CURTAINS (NO DOORS).
7- PLUMBING MUST BE CHASED OFFSIDE THE FULL RATED ASSEMBLY OF DEMISING WALLS.
8- PENDING SUBMITTAL OF REVISED/UPDATED (1/4" SCALE) FLOOR PLAN ACCOMPANIED BY ALL IMAGING EQUIPMENT & FACILITY INFO. (SIEMENS REFERENCE DWGS) NECESSARY FOR CONSTRUCTION & INSPECTIONS.
9- SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
2883 SQ FT, CALT/ STONEBRIAR IMAGING CENTER