Notes:
1- CONTINGENT UPON COMPLIANCE WITH CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- PENDING SUBMITTAL OF TDLR'S REGISTRATION NUMBER.
3- NO INSTALLATION OF RADIATION EQUIPMENT HAS BEEN INDICATED IN THE SUBMITTED DESIGN, THEREFORE NOT ALLOWED UNDER THIS PERMIT.
4- USE OF OXYGEN EQUIPMENT (OR ANY OTHER MED. GAS), AS THE POSSIBILITY IS SUGGESTED BY THE APPLICANT, IS PROHIBITED UNDER THIS PERMIT UNLESS AN APPROVED FIRE-RATED STORAGE/CONTAINMENT SYSTEM IS PROVIDED IN COMPLIANCE WITH RELATED NFPA REGULATIONS.
5- ELECTRICAL ROOM TO HAVE 1 HR RATED ENCLOSURE WITH 45 MIN. RATED DOOR SWINGING OUT AS REQ'D. (NO WATER LINES, GAS LINES OR WATER HEATER TO BE INSIDE THIS ROOM UNLESS PERMITTED BY THE ELEC. INSPECTOR).
6- PROVIDE DUAL HI/LO DRINKING FOUNTAIN OR ONE STANDARD HEIGHT D.F. PLUS ONE BOTTLED WATER COOLER CUP DISPENSER AS REQ'D.
6- SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWERS, FIRE MARSHAL AND FIELD INSPECTIONS.
5071 SQ FT, CIFO / KID LUNG