Notes:
1- CONTINGENT UPON COMPLIANCE WITH FINAL SITE PLAN APPROVALS FROM P+Z & ENGG DEPTS, BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- CONTINGENT UPON SUBMITTAL OF STATEMENT OF CODE COMPLIANCE (AS PER STANDARD FORM PROVIDED BY CITY) SIGNED & SEALED BY ALL DESIGN PROFESSIONALS AS REQ'D.
3- LOCATION & LAYOUT OF DUMPSTER ENCLOSURE MUST CONFORM TO STANDARD CRITERIA AND ALL SYSTEM APPROVED BY THE ENVIROM'L SVCS DEPT (972-335-5519) PRIOR STARTING ANY CONSTRUCTION.
4- BLDG TO BE EQUIPED WITH AUTOMATIC FIRE SPRINKLER SYSTEM SUBJECT TO FIRE MARSHAL APPROVAL.
5- VERIFY WITH P+Z IF PARKING FOR THIS BLDG (ORIGINALLY PLANNED FOR RETAIL) IS SUFFICIENT FOR MUSIC CONSERVATORY USE.
6- GUTTER DOWNSPOUTS TO BE CONNECTED DIRECTLY UNDERGROUND TO STORM SEWER AS REQ'D.
7- NO MECH'L ELEMENTS TO PLACED ON ROOF OTHER THAN SMALL INCOSPICUOUS VENTS OR FLUES WHEN APPROVED BY INSPECTORS AND PAINTED TO MATCH ROOF'S COLOR.
8- ALL EXITWAYS & CORRIDOR WALLS TO BE FULL-HEIGHT 1 HR UL-U305 OR APPROVED EQUAL, WITH PROTECTED OPENINGS AS REQ'D. (EXCEPT FOR WALLS ENCLOSING THE HIGHER SPACES OVER THE ENTRY & WAITING AREAS, CORRIDOR WALLS & OTHER RATED WALLS, MAY BE STOPPED TO UNDERSIDE OF ROOF TRUSSES WHEN 2 LAYERS OF 5/8" TYPE 'X' GYP. B'D ARE FASTENED UNDERNEATH THE TRUSSES COVERING THE RATED SPACE).
9- ADD UNISEX TOILET AND HI/LO DRINKING FOUNTAIN IN RECOMMENDED LOCATIONS. (OTHER PREFERRED LOCATIONS MAY BE PROPOSED BY ARCHITECT AND FINAL UPDATED PLAN RESUBMITTED FOLLOWING APPROVAL).
10-NO FOOD PREPARATION NOR COOKING EQUIPMENT ALLOWED IN BREAK ROOM UNLESS OTHERWISE SPECIFIED IN SEPARATE SUBMITTED DTLS APPROVED BY THE HEALTH DEPT.
11-SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
7000 SQ FT, CNEW / MUSIC CONSERVATORY OF TEXAS