Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- PERMIT IS RELEASED UNDER EXISTING OFFICE BLDG RESTRICTIONS, LIMITING THIS SPACE OCCUPANCY TO NOT MORE THAN 15 PEOPLE (EQUIVALENT TO THE CORRESPONDING OFFICE RATIO OF PKG SPACES ON SITE). THE TOTAL LIMIT OF 15 PEOPLE (CUSTOMER & EMPLOYEES) IS ALSO IMPOSED BY CODE FOR THE SINGLE UNISEX RESTROOM PROVIDED. THEREFORE, THE POSTING OF A SIGN IS REQUIRED THAT THE MAX. NUMBER OF CUSTOMERS ALLOWED IN THE ENTRY/RETAIL AREA, WHEN ADDED TO THE NUMBER OF EMPLOYEES WORKING IN THE PREMISES, DOES NOT EXCEED 15 PEOPLE.
3- VERIFY WITH ENVIRONM'L SVCS DEPT (972-335-5519) IF ANY SPECIAL PERISHABLE WASTE CONTAINMENT SYSTEM IS NECESSARY IN ADDITION TO THE EXISTING OFFICE BLDG'S SYSTEM.
4- PENDING SUBMITTAL OF ENGG DETAILS FOR THE CUTTING OF THE PROPOSED NEW DOOR OPENING THRU THE STRUCT'L TILT-UP PANEL, SIGNED & SEALED BY A STRUCT'L ENGR. (DTLS MUST INDICATE PROPER LOCATION OF OPENING WITHIN THE CONCRETE PANEL AND IF ANY ADDITIONAL REINFORCING IS NEEDED).
5- PLBG PIPES ARE NOT PERMITTED TO BE INSTALLED INSIDE A FIRE-RATED DEMISING WALL. (USE FURR-OUT PLBG CHASES OR SIDE WALLS).
6- PROVIDE HI/LO DRINKING FOUNTAIN AS REQUIRED. (LOCATION OPTIONAL BUT SUBJECT TO INSPECTOR'S APPROVAL).
7- ALL FOOD-RELATED AREAS & EQUIPMENT SUBJECT TO HEALTH & FOOD SAFETY DEPT APPROVALS.
8- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
(3/1/2005 10:25 JS) (3/1/2005 10:23 JS)GREASE INTERCEPTOR SHALL BE LOCATED OUTSIDE AND IN GROUND.
1485 SQ FT, CIFO / SUPER SUPPERS