Notes:
220 SQ FT, CIFO / MASSAGE ROOM
4/5/2005 12:00:00 AM
ommercial plan review
1. one hour fire/smoke rated construction
ELECTRICAL PLAN REVIEW NOTES:
ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.
1. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
2. NO ALUMINIM WIRE PERMITTED.
3. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
4. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2000 IBC.
5. LIGHTING AND CONTROLS SHALL COMPLY WITH 2000 IECC WHERE APPLICABLE.
ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
LICENSED SUBCONTRACTORS MUST BE REGISTERED WITH THE CITY OF FRISCO BEFORE BEGINNING ANY WORK. SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.