Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- PENDING SUBMITTAL OF ASBESTOS STATEMENT SIGNED AND SEALED BY ARCHITECT AS REQ'D.**received**
3- PENDING SUBMITTAL OF MEDICAL PHYSICIST'S REPORT ON NECESSARY SHIELDING PROTECTION OF X-RAY EQUIPMENT AREAS.
4- PROVIDE 1 HR DEMISING WALL TO DECK FIRE SEALED AS REQ'D.
5- DOOR OF RATED OXYGEN CLOSET TO BE 1 HR.
6- ELECT'L ROOM TO HAVE 1 HR PARTITIONS TO DECK (OR TO 1 HR CLG) WITH 45 MINUTE DOOR IN 1 HR FRAME.
7- PROVIDE MOP SINK AND HI/LO DRINKING FOUNTAIN AS REQ'D (LOCATION OPTIONAL).
8- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND BLDG INSPECTIONS.
(6/8/2005 14:22 MBW) PER UMBERTO, NO WORK REGARDING RADIOLOGY EQUIPMENT MAY BE DONE UNTIL THEY COMPLY WITH HIS REQUEST.
3200 SQ FT, CIFO / FRISCO E.R. CARE