Notes:
1- CONTINGENT UPON P+Z & CIVIL ENGG APPROVALS OF FINAL SITE PLAN, COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- DUMPSTER ENCLOSURE FACILITIES TO CONFORM WITH STANDARD CITY CRITERIA WITH AREA DRAINS AS REQ'D. DRIVEWAY TURNS ALONG WASTE TRUCK'S ROUTE NOT TO BE LESS THAN 20' RADIUS. NUMBER & TYPE OF FACILITIES MUST BE APPROVED BY THE ENVIRONM'L DEPT (972-292-5900) PRIOR STARTING ANY CONSTRUCTION.
3- PARKING IS BASED ON 61% MEDICAL & 39% NON-MEDICAL OFFICE = 25 SPACES FOR BLDG #1.
4- BLDG TO HAVE MIN. 20' FIRE DISTANCE FROM OTHER BLDGS UNLESS WALLS WITHIN THIS DISTANCE ARE 1 HR RATED WITH PROTECTED OPENINGS S REQ'D AND ALL ROOF AND CLG FRAMING ABOUT THESE WALLS ARE 1 HR PROTECTED AS PER SEC. 704.11, EXC. 4 OF 2000 IBC. (SEE TAB. 704.8 FOR SIZE OF OPENINGS).
5- STRUCT'L DWGS AND RELATED NOTES ARE NOT VALID UNLESS COORDINATE & RESUBMITTED WITH ALL CODE REFERENCES CORRECTED TO 2000 IBC AS REQ'D AND ALL DWGS STAMPED WITH THE ENGR'S SEAL.
6- SHELL MUST PROVIDE SPACE FOR ALL TENANTS' MECH'L EQUIPMENT TO BE TOTALLY CONCEALED UNDER ROOF. ATTIC SPACE TO BE SPRINKLER PROTECTED AND VENTILATED AS REQ'D. UNLESS A COMMON ATTIC ACCESS IS OTHERWISE PROVIDED BY THE SHELL, EACH FUTURE TENANT MAY ACCESS THE ATTIC PORTION ABOVE OWN SUITE, WHICH MUST BE TOTALLY ENCLOSED WITHIN 1 HR DEMISING WALLS UP TO ROOF DECK (SUBJECT TO APPROVAL OF FUTURE FINISH-OUT PLANS).
7- ALL CLGS TO BE 1 HR DOUBLE LAYER OF 5/8" TYPE 'X' GYP BD AS PER GA-FC 5406 0R BETTER.
8- BLDG ENVELOPE'S INSULATION IS PART OF SHELL PERMIT CONDITIONS AND SHALL BE PROVIDED TO MEET OR EXCEED YHE MIN. REQUIREMENTS OF 2000 IECC.
9- PENDING RESUBMITTAL OF ARCH'L DWGS UPDATED TO MORE SUBSTANTIAL DETAILING AND STAMPED WITH THE DESIGNER'S PROFESSIONAL SEAL AS REQ'D.
10- SUBJECT TO CONFORMING RESUBMITTAL, M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
5775 SQ FT, CNEW / STARWOOD PROFESSIONAL VILL, BLDG 1