Notes:
1903 SQ FT, CALT / BEST BUY (magnolia home theater)
7/15/2005 12:00:00 AM
3. 1 hour fire/smoke construction w/ 6” metal studs w/ 5/8” type X gypsum on both sides up to deck.
a. fully sprinklered
b. existing wall at storage area must be one hour fire/smoke rated wall assembly with existing 6" mtl. studs, 5/8" type "x" gypsum on both sides upto deck and fire sealed.
(7/15/2005 15:39 JM)
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. NO ALUMINIM WIRE PERMITTED.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2000 IBC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2000 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.