Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- UNDER THIS PERMIT, THE FUTURE OFFICE AREA #116 SHALL BE CONSIDERED AS UNUSED EMPTY SPACE UNTILL DERMINATION ON PROPER NUMBER OF EXITS IS MADE BASED ON THE FINALLY SUBMITTED SPACE DESIGN AND FURNISHING LAYOUT. AT THIS TIME THE SPACE IS TO BE 1 HR SEPARATED FROM OTHER AREAS, WITH MIN. 2 EXITS, AS REQ'D.
3-WALLS OF RECEPTION ROOM #100 MUST BE 1 HR FIRE/SMOKE RATED TO DECK MAKING THE RECEPTION AREA LIKE AN EXTENSION OF THE MAIN BLDG LOBBY. ALL DOORS TO BE 1 HR ASSEMBLY AS REQ'D. SPRINKLER PROTECTION ON BOTH SIDES OF TEMPERED GLASS SIDELIGHTS AND/OR GLASS DOORS (INCLUDING LOBBY DOORS) IS ACCEPTABLE IN LIEU OF 45 MINUTE GLAZING.
4- PIPES FOR BREAKROOM PLBG FIXTURES TO BE LOCATED INSIDE FURR-OUT SPACE (OFFSIDE THE TOILET'S DEMISING WALL) AS REQ'D.
5- CORRIDORS FORMED BY TENANT'S OFFICE CUBICLES MUST ALLOW TRAFFIC CONTINUITY AS MUCH AS POSSIBLE. (DEAD-END CORRIDORS, IF ANY, SHALL NOT BE APPROVED IF EXCEEDING 20' IN LENGTH).
6- ANY EXIT DOOR WITH KEY LOCK OR CIPHER LOCK MUST BE ABLE TO BE OPENED FROM THE INSIDE WITHOUT KEY OR SPECIAL KNOWLEDGE AS REQ'D.
7- DUCTS PENETRATING RATED WALLS TO DECK MUST BE EQUIPPED WITH FIRE/SMOKE COMBINATION DAMPERS, UNLESS OTHERWISE REQUIRED BY INSPECTORS BASED ON SPECIFIC SITE CONDITION.
8- SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
16262 SQ FT, CIFO / CALPONT