Notes:
2257 SQ FT, CIFO / MOODY NATIONAL
10/14/2005 12:00:00 AM
1. valid 1 hour fire/smoke connection to mullion.
2. 1 hour fire/smoke construction w/ 3 5/8” metal studs w/ 5/8” type X gypsum on both sides up to deck, and fire seal fin. floor to deck.
3. fully sprinklered.
4. fire/smoke dampers in hallway.
5. one hour corridor.