Notes:
2134 SQ FT, CIFO / DR CHINOY-ALLERGY & ASTHMA SOLUTIONS
1/4/2006 12:00:00 AM
1. 1 hour fire/smoke construction w/ 6” metal studs w/ 5/8” type X gypsum on both sides up to deck--this is existing demising wall--fire seal floor to deck.
2. Need high/low drinking fountain--letter is submitted stating that doctor will provide bottled water.
3. provide fire extinguisher at dead end corridor
4. no locks at break rm. permitted in case of fire.
5. doors at restrooms must swing out to be ADA compliant, also one door at break rm. must swing out.
6. tempered windows at entry.
7. fully sprinkled.
8. construction is subject to field inspection approval.
(2/20/2006 08:50 MBW) CHANGED TO BUILDING #3 FROM #8 PER OWNER REQUEST.