Notes:
125900 SQ FT, CIFO / T-MOBILE TECHNICAL CARE CENTER
3/24/2006 12:00:00 AM
1. 1 hour fire/smoke connection to mullion.
2. 1 hour fire/smoke construction w/ 3 5/8” metal studs w/ 5/8” type X gypsum on both sides up to deck.
3. 1 hour doors at 1 hr. enclosures, elevator lobbies, stairs, mdf room.
4. kitchen 36" minimum egress between tables
5. 3rd floor additional egress at open office area (more than 50' dead end corridor) IBC 2003 1016. 3 ex. 2
6. type 1 vent hood at kitchen with 1 hour shaft enclosure or 1 hr. fire wrap IMC 2003 506.
7. fully sprinkled.
8. all work subject to field app'd. inspection
(3/24/2006 18:39 JM)
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. NO ALUMINIM WIRE PERMITTED.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2000 IBC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2000 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.
(3/27/2006 08:13 JS) 3/27/2006 08:12 JS)
PLEASE COMPLY WITH HEALTH ORDINANCE # 00-03-19 AND SMOKING ORDINANCE #00-12-12.
(3/27/2006 08:12 JS)
SEE ALL NOTES FOR FOOD SERVICE ON B06-1021.