Notes:
1- CONTINGENT UPON COMPLIANCE TO BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- NO PLBG ALLOWED INSIDE 1 HR DEMASING WALL.
3- UNLESS ALREADY PROVIDED WITH SHELL PERMIT, ATTIC'S FLOOR FRAMING TO BE 1 HR PROTECTED WITH DOUBLE LAYER OF 5/8" TYPE 'X' GYP. BD TO UNDERSIDE OF JOISTS AND BMS. ANY PARTITIONS OR COLUMNS SUPPORTING RATED FLOOR FRAMING TO BE 1 HR RATED AS REQ'D.
4- MECH'L/ELECT'L ROOM #121 TO BE 1 HR RATED (WALL & CLG) WITH 1 HR RATED DOOR SWINGING OUT.
5- PROVIDE HI/LO DRINKING FOUNTAIN AS REQ'D. SUBSTITUTIONS WITH BACTERIA-FREE BOTTLED WATER COOLER WITH CUP DISPENSER, WHEN REQUESTED IN WRITING BY DOCTOR, MAY BE ACCEPTABLE, BUT WILL ACCOUNT ONLY AS THE LOW PART OF THE ASSEMBLY, THEREFORE, THE ADDITIONAL INSTALLATION OF ONE STANDARD-HEIGHT D.F. WOULD STILL BE REQ'D.
6- PROVIDE FIRE/SMOKE COMBINATION DAMPERS AT ALL DUCT'S RATED PENETRATIONS UNLESS OTHRWISE REQUIRED BY INSPECTORS.
7- NO EXTERIOR MECH'L EQUIPMENT TO BE VISIBLE OTHER THAN INCONSPICUOUS SMALL VENTS OR FLUES WHEN APPROVED BY INSPECTORS AND PAINTED TO MATCH OF THE COLOR OF ADJOINING MATERIAL.
8- SUBJECT TO MORE REQUIREMENTS FROM MEP REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
3935 SQ FT, CIFO / WISE ORTHODONTICS