Notes:
4166 SQ FT, CALT / UNIVERSAL BILLIARDS
8/2/2006 12:00:00 AM
1. Subject upon field inspection.
2. See notes on approved set of plans for compliance.(7/18/2006 15:48 PPB)
Comments and requirements:
1. The plans shows that two existing space will be combined into one space, that makes the spaces NOT in compliance with codes;
a.) the total area of the combined space is 4166 sqft., therefore the main entrance doors shall be provided with vestibules as per IECC 802.3.6. Submit revised floor plan showing vestibule for both spaces.
b.) the occupant load is more than 50 people therefore 2 exits are required and must be placed at least 1/2 of the total diagonal distance of the area serve, egress from a space is prohibited to enter in a storage/stockroom or a room that can be locked/permanently closed. Submit revised floor plan for both spaces showing this requirements.
2. Submit Asbestos report from the Design Professional or licensed person from state health department .
3. Submit a signed code compliance form from the design professional.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.