Notes:
4145 SQ FT, CIFO / DRUG CRAFTERS
8/30/2006 12:00:00 AM
THE ARCHITECT IN DRUG CRAFTERS PROJECT SUBMIT THE MSDS SUMMARY AND A LETTER , THEREFORE 1-HOUR FIRE BARRIER IS NOT REQUIREDFOR CHEMICAL STORAGE ROOM 109 AND 107.
(7/26/2006 14:37 PPB)
Plan review comments;
1. The storage/shipping/chemical/quarantine area shall be separated from the rest of the space by at least 1-hour fire barrier wall construction with 45 minutes fire rated doors (see IBC 414.2.4 & T-414.2.2). See notes on plans.
2. Safety glazing required as per IBC 2406.
3. Fire/Smoke dampers required where ducts penetrates the fire barrier wall.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.