Notes:
4500 SQ FT, CIFO / MATTRESS GIANT
8/25/2006 12:00:00 AM
Plan review comments;
1. Vestibule is required on all exterior entrance door that is open to a 3000 sqft area. Submit revised floor plan showing vestibule.
2. Smoke partition wall required between sales/corridor and stockroom and duct penetration through the wall shall have smoke dampers. Submit wall section with details.
3. Vinyl composition tile and paint on gypsum board is not allowed in walls, floors of restrooms. The code specify a smooth, hard, and non-absorbent surface materials are only allowed. submit revised finish schedule.
4. New demising wall shall be 1-hour fire resistive construction and any penetrations to it shall not reduced its fire resistance rating, also submit detail of wall connection between the fire rated demising wall and the exterior glazing.
5. MEP shall be signed and sealed by Professional Engineer or its individual licensed person on that trade
6. Subject to field inspection.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.