Notes:
63000 SQ FT, CADD / COLLIN COUNTY COMMUNITY COLLEGE BLDG D
10/2/2006 12:00:00 AM
PLAN REVIEW COMMENTS;
1. APPLICABLE CODES SHOULD BE IN 2003 IECC, IMC, IPC AND 2002 NEC.
2. THE MAIN LOBBY AREA OPEN TO EXIT ACCESS CORRIDOR SHALL HAVE AT LEAST 1- HOUR FIRE BARRIER WALL FROM FIRST FLOOR UPTO THE ROOF DECK IN ORDER NOT TO DIMINISHED THE LEVEL OF FIRE PROTECTION RATING REQUIRED.
3. IN THE PLAN THE VERTICAL EXIT STAIRWAYS ENCLOSURE WAS NOT CALLED OUT TO HAVE A 1-HOUR FIRE RATED CONSTRUCTION, THERE WAS SOME DETAIL BUT NOT SPECIFICALLY CALLED IN THE PLANS.
4. FOR A BUILDING TO BE CONSIDERED "EQUIPPED THROUGHOUT" WITH AN NFPA SPRINKLER SYSTEM, COMPLETE PROTECTION MUST BE PROVIDED IN ACCORDANCE WITH IBC 903.3.1.1 SUBJECT TO EXEMPT LOCATIONS INDICATED IN IBC 903.3.1.1.1, THEREFORE IF SPRINKLER SYSTEM IS NOT INSTALLED "THROUGHOUT" THE PROVISION TO HAVE AN AREA INCREASE WILL NOT BE GRANTED AND THE BULDING WILL BE MORE THAN THE ALLOWABLE AREA.
5. SHEET A02-03A HAS NO MATCHING DRAWING IN SHEET A02-05.
6. SOLAR HEAT GAIN COEFFICIENT (SHGC) SHALL BE 0.40 MAXIMUM.
7. AN APPROVED PROTECTIVES SHALL BE PROVIDED FOR OPENING THAT IS LESS THAN 15 FEET VERTICALLY ABOVE THE ROOF OF ADJACENT STRUCTURE.
8. FIXED GLAZING (SIDE LITE) LOCATED IN THE CORRIDOR WITHIN 24" FROM THE DOOR SHALL BE PROTECTED BY AT LEAST 45 MINUTES FIRE PROTECTION RATING.
9. SAFETY GLAZING AS REQUIRED IN 2003 IBC 2406.
10. MECHANICAL EQUIPMENTS (EXHAUST FLUME) SHALL BE SCREENED COMPLETELY.
11. ANY WOODS USED IN TYPE II-B CONSTRUCTION SHALL BE FIRE RETARDANT TREATED WOOD.
12. IN 2003 IECC A VESTIBULE IS REQUIRED ON ALL EXTERIOR DOOR THAT IS OPEN TO 3000 SQFT OF CONDITION SPACE.