Notes:
3591 SQ FT, CNEW /ELDORADO BNSF PUMP STATION
10/13/2006 12:00:00 AM
ALL WORK PERFORMED MUST MEET THE 2003 IBC STANDARDS.
SUBJECT TO FIELD INSPECTION APPROVAL.
CALL (972) 292-5386 FOR INSPECTION.
(10/16/2006 13:12 JM)
MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS. NO ALUMINIM WIRE PERMITTED. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2003 IBC. LIGHTING AND CONTROLS SHALL COMPLY WITH 2000 IECC WHERE APPLICABLE. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.
(RTU -2 use 2 #8's w/ 1# 10 grd. #10 awg is too small )