Notes:
1080 SQ FT, CIFO / PACIUGOS ICE CREAM
12/22/2006 12:00:00 AM
PLAN REVIEW COMMENTS;
1. CITY OF FRISCO ORDINANCE THAT ALL MECHANICAL EQUIPMENTS SHALL BE SCREENED, THEREFORE THE EXHAUST FAN SHALL BE DISCHARGE OUT ABOVE THE ROOF NOT INTO THE OUTSIDE WALL.
2. RETURN AIR SHALL NOT BE TAKEN FROM THE KITCHEN AREA (IMC 918.6 #5).
3. 1-HOUR FIRE RATED DEMISING WALL REQUIRED BETWEEN TENANT SPACES.
4. SAFETY GLAZING REQUIRED ON DOORS AND STOREFRONT GLAZING AS PER 2003 IBC 2406.3.
5. RESTROOM FLOORS AND WALLS SHALL HAVE A SMOOTH, HARD AND NON-ABSORBENT SURFACE (IBC 1210).
6. WALL AND CEILING FINISHES SHALL COMPLY WITH IBC TABLE 803.5 FOR THEIR FLAME SPREAD RATING AND SMOKE DEVELOPED INDEX REQUIREMENTS.
7. SUBJECT TO FIELD INSPECTION.
8. SUBMIT SITE PLAN, SPACE LOCATION PLAN, AND ARCHITECTURAL PLAN AND DETAILS.
(12/22/2006 15:47 JS) NOTES ON AMENDMENT SET. FLOOR, WALL, CEILING, COUNTER, CABINET FINISHES MUST MEET HEALTH ORDINANCE #06-10-102 REQUIREMENTS; ALL LIGHTING IN FOO PREP, STORAGE, DISPLAY AND WAREWASH AREAS SHALL BE SHATTERPROOF OR COVERED; MOP SINK MUST BE FLOOR MOUNTED CURBED FACILITY; SMOKING SIGNAGE REQUIRED PER SECTION 6 OF ORD#00-12-12 AT EACH ENTRANCE; 500 GALLON INTERCEPTOR APPROVED; PROVIDE DEDICATED AND SEPARATE FOOD PREPARATION SINK; WATER HEATER MUST BE EQUAL TO: 10.3 KW 56 GPH, SEE ATTACHED SCHEDULE.
(1/5/2007 14:57 MBW) CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.