Notes:
8400 SQ FT, SCHA / CENTENNIAL HIGH SCHOOL CTE BUILDING
11/16/2006 12:00:00 AM
PALN REVIEW COMMENTS;
1. THE BUILDING IS CLASSIFIED AS MIXED USED OCCUPANCY OF GROUP E (EDUCATION) AND GROUP S-1 (VOCATIONAL/REPAIR GARAGE) THEREFORE THE CMU WALL BETWEEN GROUP E AND S-1 SHALL BE AT LEAST 1-HOUR FIRE RATED CONSTRUCTION AND DOOR OPENINGS SHALL BE PROTECTED BY 60 MINUTES (SELF CLOSING) AND WINDOWS WITH 45 MINUTE FIRE RATED ASSEMBLY.
2. THE INCEDENTAL USES SUCH AS THE TOOL ROOMS, OFFICES, FIRE RISER AND TECH LAB. ROOMS SHALL BE SEPARATED BY 1-HOUR FIRE BARRIER OR SMOKE BARRIER AND DOORS SHALL BE SELF CLOSING OR AUTOMATIC.
3. WALL AND CEILING FINISH SHALL HAVE A FLAME SPREAD RATING OF AT LEAST 76 TO 200; SMOKED DEVELOPED 0 TO 450.
4. LEADERS/DOWNSPOUT AND OUTSIDE AIR LOUVER SHALL BE PAINTED AS TO MATCH THE EXTERIOR FINISH AS PER ZONING ORDINANCE.
5. TOTAL PLUMBING FIXTURES SHALL BE 4 W.C. AND 4 LAVATORIES THEREFORE SHORT OF 2 W.C. AND 2 LAV.. SUBMIT RESTROOM PLAN.
6. SAFETY GLAZING REQUIRED IN WINDOW 02, DOORS B AND C.
7. HI/LO DRINKING FOUNTAIN REQUIRED.
8. ANY MECHANICAL EQUIPMENT SHALL BE COMPLETELY SCREENED AS PER COF ORDINANCE.
9. FIRE/SMOKE DAMPERS REQUIRED ON ALL DUCTS THAT PENETRATES THE 1-HOUR FIRE RESISTIVE WALL CONSTRUCTION.
10. SUBJECT TO FIELD INSPECTION.