Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- OPEN OFFICE AREAS 3130 & 3140 TO BE SEPARATED IN TWO SMOKE ZONES BY 1 HR WALLS, WHERE POSSIBLE, OR WITH 1 HR FURR-DOWN SMOKE VALANCE FROM MIN. 1'-0" BELOW LOWEST CLG AND PROTECTED BY SPRINKLER HEADS @ MAX. 4'-0" O/C ALONG BOTH SIDES. RATED VALANCE MUST CONTINUE UP TO UNDERSIDE OF ROOF DECK AND FULLY FIRE SEALED AS REQ'D.
3- BLDG'S CORRIDOR MUST BE CONTINUOUS 1 HR EXITWAY, FROM MAX. 20' WEST OF STAIR #1 EXIT, TO ELEVATOR LOBBY, IN COORDINATION WITH CONSTRUCTION OF LOBBY ENCLOSURE (BY OTHERS) AND EXACT CONNECTING LOCATION OF CORRIDOR DOORS #3101, WHICH MUST BE 1 HR FIRE/SMOKE & DOUBLE-EGRESS TYPE (WITH PUSH SIDE ON THE RIGHT).
4- MTL STUDS, OF RATED OR UNRATED PARTITIONS, SPANNING FULL HEIGHT FROM FLOOR TO DECK ABOVE MAY NOT TO BE LESS THAN 3-5/8"x20 GA @ 16" O/C. BECAUSE THE ROOF DECK MAY NOT BE PERFORATED, TOP OF STUDS MUST BE SECURED LATERALLY TO THE ROOF'S FRAMING ELEMENTS. SHORTER FLOOR-TO-CLG PARTITIONS MUST BE DIAGONALLY BRACED TO ROOF FRAMING ONLY WITH NO ATTACHEMENTS WHATSOEVER TO CLG GRID.
5- DUCT PENETRATIONS OF RATED WALLS TO BE PROVIDED WITH FIRE/SMOKE COMBINATION DAMPERS AND ALL GAPS FIRE SEALED AS REQ'D.
6- FLOOR ELECT'L OR ELECTRONIC OUTLETS MUST BE CORE-DRILL INSTALLED UL-RATED POKE-THRU DEVICES AS PER APPROVED (CATALOG CUT) DTLS.
7- SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
WARNING NOTE:
BECAUSE NO COPY OF REVIEWED DWGS IS KEPT BY THE CITY, OWNER (OR OWNER'S REPRESENTATIVE) AND/OR CONTRACTORS ARE RESPONSIBLE FOR PRINTING THEIR OWN RECORDS AND BE ABLE TO PROVIDE A REPLACEMENT COPY IN CASE THE RELEASED MARKED PERMIT SET IS LOST, DAMAGED OR UNAVAILABLE AT THE JOB SITE. OTHERWISE, CONSTRUCTION MAY NOT CONTINUE UNTIL DWGS ARE RESUBMITTED FOR NEW PERMIT AND RELATED ADDITIONAL REVIEW FEES ARE PAID.
14782 SQ FT, CIFO / T-MOBILE