Notes:
4000 SQ FT, CIFO / CATWALK
11/10/2006 12:00:00 AM
PLAN REVIEW COMMENTS;
1. THE OCCUPANT LOAD FOR THE SPACE UNDERCONSIDERATION SHALL BE ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3, THEREFORE BASED ON THE FLOOR PLAN SUBMITTED THE LARGEST OCCUPANT LOAD WAS BASED ON THE ACTUAL NUMBER COUNT WHICH IS 117 PERSONS.
2. SINCE THE OCCUPANT LOAD WAS OVER 50 PEOPLE 2 MEANS OF EGRESS ARE REQUIRED, THE SECOND MEANS OF EGRESS THAT WILL ACCESS INTO A BREAKROOM IS NOT ALLOWED (IBC 1013.2) THEREFORE PROVIDE AT LEAST A CLEAR PATH OF TRAVEL BETWEEN DOOR 105 TO 106 BY PAINTING THE FLOOR WITH STRIPED AND SHALL NOT BE USED AS STORAGE AT ALL TIMES.
3. THE NUMBER OF PLUMBING FIXTURES FOR WATER CLOSETS SHALL 4 IN TOTAL, 2 WATER CLOSETS PER SEXES, THEREFORE PROVIDE REVISED FLOOR PLAN THAT SHOWS COMPLIANCE WITH THE CODE (IBC TABLE 2902.1).
4. RESTROOMS FLOOR FINISH SHALL HAVE A SMOOTH, HARD AND NON-ABSORBENT SURFACE AS REQUIRED IN IBC1210.1.
5. PENETRATIONS ON A 1-HOUR FIRE RATED DEMISING WALL SHALL NOT REDUCED IT'S FIRE RESISTIVE RATING (IBC 712).
6. IN A SALON USED AS A BEAUTY SHOP WHERE CHEMICALS SUCH AS AEROSOL SPRAYS ARE ROUTINELY USED SHALL BE PROVIDED WITH A DIRECT-VENT APPLIANCES (IFGC 304.12).
7. ON THIS PARTICULAR SPECIALTY SHOPS "SALON" SHALL BE PROVIDED WITH AN OUTSIDE VENTILATION AIR OF AT LEAST 25 CFM PER PERSON (IMC TABLE 403.3), SO AT LEAST 2500 CFM SHALL BE PROVIDED BUT THE 3 UNITS ONLY PROVIDES 1800 CFM COMBINED THEREFORE THE SYSTEM IS SHORT OF 700 CFM MORE.
8. HI/LO DRINKING FOUNTAIN AND MOP SINK AS REQUIRED IN IPC TABLE 403.1.
(3/9/2007 16:04 MBW) CORRECTED ADDRESS TO 3880 FROM 3550 PARKWOOD BLVD.