2433 SQ FT, CIFO / KRISTEN INNES MEDICAL OFFICE
12/8/2006 12:00:00 AM
PLAN REVIEW COMMENTS;
1. CONNECTION OF 1-HOUR FIRE DEMISING WALL TO A GLASS IS NOT ALLOWED, THEREFORE REPLACE THE GLASS WITH A WALL THAT IS THE SAME TYPE OF CONSTRUCION.
2. WATER CLOSET BOWLS SHALL BE ELONGATED TYPE.
3. SAFETY GLAZING REQUIRED.
4. ANY MEMBRANE PENETRATION ON THE DEMISING WALL SHALL BE INSTALLED NOT TO REDUCED THE 1-HOUR FIRE RESISTANCE RATINGS.
5. WALL AND CEILING FINISH SHALL HAVE A FLAME SPREAD RATING OF 76-200, SMOKED DEVELOPED 0-450.