Notes:
3078 SQ FT, CIFO / DR MATT CHALMERS
1/5/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. APPLICABLE CODES SHALL BE THE 2003 IECC, IPC, IMC AND IFGC NOT THE 2000 EDITION.
2. SINCE THE PROPOSED DOCTOR'S OFFICE HAS AN X-RAY ROOM A REPORT FROM TDH LICENSED PROFESSIONAL MEDICAL PHYSICIST IS REQUIRED AND MUST INDICATE ALL THE SPECIAL PROTECTIVE CONSTRUCTION THAT THE PHYSICIST HAS RECOMMENDED.
3. STOREROOM IS AN INCIDENTAL USE TO THIS SPACE AND MUST BE SEPARATED FROM THE REST OF THE BUILDING BY A SMOKE PARTITION CONSTRUCTION.
4. DUCT PENETRATION INTO THE SMOKE PARTITION SHALL BE PROVIDED WITH SMOKE DAMPERS.
5. FLEXIBLE DUCT THAT PENETRATE THE SMOKE PARTITION IS PROHIBITED.
6. FLOORS AND WALLS SHALL HAVE A SMOOTH, HARD, AND NON-ABSORBENT SURFACE.
7. INTERIOR CEILING AND WALL FINISHES SHALL HAVE A FLAME SPREAD INDEX OF 0-200 AND SMOKED DEVELOPED INDEX OF 0-450.
8. PLANNING AND ZONING ORDINANCE THAT ALL MECHANICAL EQUIPMENTS SHALL BE COMPLETELY SCREENED FROM SIGHT.
9. ANY WOODS USED IN A TYPE II-B CONSTRUCTION SHALL BE FIRE RETARDANT TREATED WOOD.
10. SUBJECT TO FIELD REVIEW AND INSPECTION.
11. LETTER SHOULD SPECIFY THAT FREE BOTTLED DRINKING WATER WILL BE PROVIDED AT ALL TIMES TO ALL PERSON USING THE SPACE.