Notes:
4118 SQ FT, CALT / JC PENNEY (SEPHORA COSMETICS)
1/19/2007 12:00:00 AM
1. APPLICABLE CODES SHALL BE 2003 IECC,IPC,IMC.
2. ALL MATERIALS SHALL BE OF NON-COMBUSTIBLE DUE TO THE TYPE II-B CONSTRUCTION CLASSIFICATION.
3. ALL WALLS AND CEILING FINISH SHALL MEET FLAME SPREAD RATING AND SMOKE INDEX RATING REQUIRED IN 2003 IBC SECTION 803.
4. SPACE ABOVE CEILING USED AS A PLENUM SHALL BE OF NON-COMBUSTIBLE MATERIALS.
5. SMOKE DAMPER REQUIRED IN THE STOCKROOM WALL WHERE THE NEW DUCT PENETRATES.
6. SUBJECT TO FIELD REVIEW AND INSPECTION.
(1/23/2007 09:27 JM)
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. NO ALUMINIM WIRE PERMITTED.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2003 IBC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2003 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.