PLAN REVIEW COMMENTS;
1. THE OCCUPANT LOAD FOR THIS SPACE IS 22 PEOPLE NOT 11, CUSTOMER AREA = 246 SQFT / 15 (FACTOR) = 17 PEOPLE AND KITCHEN AREA = 874 SQFT / 200 (FACTOR) = 5 PEOPLE WHERE THE TOTAL IS 22 PEOPLE (IBC TABLE 1004.1.2). SUBMIT REVISED PLAN
2. DOOR EGRESS NUMBER 4 DOES NOT HAVE CLEAR EXIT PASSAGEWAY LOOKS LIKE PASSING TO AN INTERVENING ROOM OR SPACE AND THE CODE DOES NOT ALLOW IT (IBC 1013.2). SUBMIT REVISED PLAN THAT SHOWS CLEAR EXITING FROM THE SPACE.
3. SEPARATE RESTROOM FACILITIES REQUIRED FOR EACH SEX WHERE THE OCCUPANT LOAD IS 15 OR MORE (IBC 2902.2). SUBMIT REVISED PLAN.
4. PENETRATIONS ON THE FIRE RATED WALL CONSTRUCTION SHALL BE INSTALLED AS TESTED IN AN APPROVED FIRE-RESISTANCE RATED ASSEMBLY WITH APPROVED FIRESTOP SYSTEM (IBC 712.3).
5. GREASE DUCT ENCLOSURE SHALL BE AT LEAST 2-HOUR FIRE RATED CONSTRUCTION NOT 1-HOUR.
6. MECHANICAL OUTDOOR AIR INTAKE OPENINGS OF RTU1, SHALL BE LOCATED A MINIMUM OF 10 FEET APART FROM EF-1 AND KEF1 AND ANY HAZARDOUS OR NOXIUS CONSTAMINANTS SUCH AS EXHAUST VENTS, PLUMBING VENTS..... (IMC 401.5.1).
1248 SQ FT, CIFO / CUSTER HOT DONUTS