PLAN REVIEW COMMENTS;
1. FLOOR PLAN SHALL BE DRAWN IN SUFFICIENT CLARITY, SUBMIT REVISED PLAN SHOWS WHAT THE INTENT OF USE ON EACH INDIVIDUAL SPACE ON THE PROPOSED PLAN.
2. IF THE SPACE IS USED FOR VEHICLE TO BE DRESSED-UP (TINT) IT WILL BE CLASSIFIED AS GROUP S2 AND THE SPACE SHALL BE SEPARATED BY AT LEAST 1-HOUR FIRE RESISTIVE CONSTRUCTION FROM THE REST OF THE BUILDING. SPACE SHALL BE PROVIDED ALSO WITH PROPER MECHANICAL EXHAUST SYSTEM AND THE EXISTING HVAC LAY-OUT NEEDS TO SUBMITTED IN ORDER TO BE CHECKED IF ITS STILL IN COMPLIANCE. MAKING THE SPACE AS VEHICLE WORKING AREA WILL CREATE THE SPACE NOT IN COMPLIANCE WITH THE ENERGY CODE. THEREFORE SUBMIT DRAWINGS THAT WILL MEET ALL THE INTENT OF THE CODE.
3. TWO PUBLIC ACCESSIBLE RESTROOMS REQUIRED ON THIS SPACE.
4. HI/LO DRINKING FOUNTAIN REQUIRED ON THIS SPACE.
5. THE BUILDING IS REQUIRED TO HAVE FIRE SPRINKLER SYSTEM THEREFORE THE SPACE SHALL HAVE FIRE SPRINKLER SYSTEM.
1619 SQ FT, CIFO / FRISCO TINTS