1649 SQ FT, CIFO / DR. THOMAS TRAN
2/19/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. THE ISSUE ABOUT THE X-RAY ROOM WITH A RADIATION MACHINE FOR HUMAN USE, PERFORMANCE OF EXPOSURE RATE OR DOSE MEASUREMENTS TO DETERMINE COMPLIANCE WITH EXPOSURE RATE OR DOSE MEASUREMENTS OF DIAGNOSTIC RADIATION MACHINE MUST BE PERFORMED BY A LICENSED MEDICAL PHYSICIST (TRCR 25 TAC 289.226 #9). SINCE THE CITY OF FRISCO (BUILDING INSPECTION DEPARTMENT) DOES NOT KNOW WHAT KIND, TYPE AND SPECIFICATION OF THE X-RAY MACHINE IS GOING TO BE USED A MEDICAL PHYSICIST REPORT IS REQUIRED.
2. REPLACING THE WINDOW AT THE BREAKROOM AREA TO BE USED AS AN EXIT WILL REQUIRE THE EXISTING ADJACENT WINDOWS TO BE SAFETY GLASS, GLASS DOOR SHALL HAVE SAFETY GLAZING ALSO.
3. PENETRATIONS ON A 1-HOUR FIRE RATED DEMISING WALL CONSTRUCTION SHALL BE INSTALLED AS TESTED IN AN APPROVED FIRE RATED ASSEMBLY WITH AN APPROVED FIRE-STOPPED SYSTEM.
4. FLOORS AND WALLS IN THE RESTROOM SHALL HAVE HARD, SMOOTH AND NON-ABSORBENT SURFACE.
5. DEMISING WALL SHALL BE AT LEAST 1-HOUR FIRE RESISTIVE CONSTRUCTION FROM FLOOR TO ROOF DECK, TAPED AND WITH FIRE SAFING INSTALLED.