Notes:
12217 SQ FT, CIFO / ANDERSON'S FURNITURE
3/26/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. OTHER EXTERIOR DOORS THAT WILL NOT BE USED AS AN ENTRANCE DOOR SHALL NOT BE ACCESIBLE FROM THE OUTSIDE IN ORDER NOT TO PROVIDE AN ENCLOSED VESTIBULE.
2. DOOR A9 SHALL HAVE SELF CLOSING DEVICE AND IT SHALL NOT BE UNDERCUT TO PREVENT AIR TRANSFER.
3. SUPPLIES 12 SHALL BE SEPARATED BY AT LEAST 1-HOUR FIRE RESISTIVE WALL CONSTRUCTION UPTO DECK.
4. SAFETY GLAZING AS REQUIRED IN 2003 IBC 2406.
5. APPLICABLE CODES SHALL BE 2003 ICC CODES - IBC, IMC, IPC, IECC, and IFGC.
6. CONTINGENT UPON COMPLIANCE TO BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
7. NO WORK IS ALLOWED TO BE ADDED TO, OR MODIFIED FROM, WHAT SHOWN IN PERMIT SET, UNLESS FOLLOW-UP REVISIONS ARE SUBMITTED AND APPROVED AS REQ'D.
8. ALL CEILING AND WALL FINISHES SHALL COMPLY WITH 2003 IBC SECTION 803 FOR FLAME AND SMOKE SPREAD INDEX/RATING.
9. ANY WOODS SHALL BE FIRE RETARDANT WOOD ON A TYPE II-B CONSTRUCTION AS REQUIRED BY CITY OF FRISCO.
10. ACCEPTABILITY OF USE, LAYOUT AND TYPE OF CONSTR'N OF NEWLY CREATED SPACES (NOT IDENTIFIED ON PLANS) SUBJECT TO INSPECTOR'S VERIFICATION & APPROVALS.
11. SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
NOTICE:
FOR FURTHER FILING, PLEASE SUBMIT DWGS OF MORE MANAGEABLE SIZES ( 24"x36"). (BIGGER DWGS ARE NOT ACCEPTABLE BY ESTABLISHED CRITERIA)!
(5/17/2007 14:33 MBW) CHANGED ADDRESS TO 7946 SH 121 BLDG-D FROM SUITE #100 PER BUSINESS OWNER REQUEST.