Notes:
1. ENCLOSED VESTIBULES IS REQUIRED AT MAIN ENTRANCE DOOR AS PER ENERGY CODE RQUIREMENT.
2. HI/LO DRINKING FOUNTAIN REQUIRED.
3. APPLICABLE CODES SHALL BE 2003 ICC CODES - IBC, IMC, IPC, IECC, and IFGC.
4. CONTINGENT UPON COMPLIANCE TO BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
5. ANY PATCHWORK ON THE DEMISING WALL MUST BE RATED TO MATCH EXISTING (MIN. 1 HR UL-U465), UP TO UNDERSIDE OF DECK ABOVE (AS APPLICABLE), FULLY FIRE SEALED ON BOTH SIDES.
6. ALL CEILING AND WALL FINISHES SHALL COMPLY WITH 2003 IBC SECTION 803 FOR FLAME AND SMOKE SPREAD INDEX/RATING.
7. PENETRATION ON A FIRE RATED DEMISING WALL SHALL NOT BE REDUCED ITS FIRE RESISTANCE, FIRESTOP SYSTEM SHALL BE INSTALLED AND MATERIALS SHALL BE TESTED IN AN APPROVED ASSEMBLY.
8. NO WORK IS ALLOWED TO BE ADDED TO, OR MODIFIED FROM, WHAT SHOWN IN PERMIT SET, UNLESS FOLLOW-UP REVISIONS ARE SUBMITTED AND APPROVED AS REQ'D.
9. SAFETY GLAZING REQUIRED AS PER IBC 2406.
10. ACCEPTABILITY OF USE, LAYOUT AND TYPE OF CONSTR'N OF NEWLY CREATED SPACES (NOT IDENTIFIED ON PLANS) SUBJECT TO INSPECTOR'S VERIFICATION & APPROVALS.
11. SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
****permit is for spec space only. finish-out to be permitted under seperate application****
3100 SQ FT, CIFO / SPEC SPACE