Notes:
6225 SQ FT, CIFO / GM SOUTHWEST
5/21/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. FILE ROOMS 115 AND 86 ARE INCIDENTAL AREAS (IBC 302.1.1 AND 302.1.1.1) SHALL BE SEPARATED FROM THE REST OF THE BUILDING BY AT LEAST 1-HOUR FIRE RATED WALL AND FLOOR CEILING CONSTRUCTION WITH 45 MINUTES FIRE RATED DOOR.
2. DOORS B AT NORTH SIDE OF THE BUILDING DOESN'T COMPLY WITH MANUEVERING CLEARANCES FOR MANUAL SWINGING DOORS AS REQUIRED IN ANS A1117.1 SECTION TABLE 404.2.4.1. SUBMIT REVISED FLOOR PLAN SHOWING COMPLIANCE OR COMPLY AS RED MARKED ON THE PLANS.
3. SINCE THERE IS NO SUFFICIENT DETAIL SUBMITTED THE SPACE IS REQUIRED TO BE ADA COMPLIANT.
4. HI\LO DRINKING FOUNTAIN REQUIRED. SUBMIT REVISED PLAN SHOWING LOCATION (IBC TABLE 2902.1, IBC 1109.5) OR COMPLY AS RED MARKED ON THE PLANS.
5. SUBMIT U.L DESIGN NUMBER WITH DETAIL FOR THE 1-HOUR FIRE RATED WALL AND FLOOR/CEILING ASSEMBLIES.
6. PENETRATIONS IN A 1-HOUR FIRE RATED WALL SHALL BE INSTALLED SUCH THAT THE REQUIRED FIRE RESISTANCE WILL NOT BE REDUCED (IBC 712).
7. BI-LEVEL SWITCHING SHALL BE PROVIDED AS REQUIRED IN IECC.
8. AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT IS REQUIRED.
9. SUBJECT TO FIELD REVIEW AND INSPECTION.