7500 SQ FT, CIFO / ZURI FURNITURE, LLC
6/6/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. ARCHITECTURAL, M.E.P. PLANS SHALL NOT BE FOR BID IT SHOULD BE SPECIFY FOR CONSTRUCTION.
2. IN 2003 IECC 802.3.6 ANY DOORS IN THE EXTERIOR WALL THAT SEPARATE CONDITION SPACE FROM THE OUTSIDE SHALL BE PROVIDED WITH ENCLOSED VESTIBULE UNLESS DOORS 02 ARE NOT OPENABLE FROM THE OUTSIDE OF THE BUILDING VESTIBULE WILL NOT BE REQUIRED .
3. HI/LO DRINKING FOUNTAIN REQUIRED MEETING ADA REQUIREMENTS.
4. MOP SINK REQUIRED AS PER IPC.
5. SAFETY GLAZING AS REQUIRED IN IBC 2406.
6. STORAGE ROOM IS AN INCIDENTAL USE SHALL BE SEPARATED BY A SMOKE PARTITION FROM THE MAIN SALES AREA AND DOOR 05 SHALL HAVE A SELF CLOSING DEVICE AND NO AIR TRANSFER OPENINGS.
7. PORTION OF THE RECEPTION COUNTERS SHALL BE ADA COMPLIANT.
8. NEW SKYLIGHTS SHALL BE TESTED AND LABELED AS COMPLYING WITH 101/I.S.2/NAFS VOLUNTARY PERFORMANCE SPECIFICATION FOR WINDOWS, SKYLIGHTS AND GLASS.
9. SUBJECT TO FIELD REVIEW AND INSPECTION.
10. CONTINGENT UPON P+Z & CIVIL ENGG APPROVALS OF FINAL SITE PLAN, COMPLIANCE TO BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. NO ALUMINIM WIRE PERMITTED.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2003 IBC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2003 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.
see revision dwgs. attached to back of plans: sheet E1, E2, A2, P1