Notes:
1185 SQ FT, CIFO / MAXWELL'S CLEANERS
6/8/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. PUBLIC CORRIDOR SHALL BE CONSTRUCTED BY AT LEAST 1-HOUR FIRE RATED WALL PARTITION FROM FLOOR TO DECK ABOVE AND MUST BE INCLUDED IN THE PROJECT BECAUSE IT IS PART OF EGRESS REQUIREMENT. DOOR #5 SHALL HAVE 20 MINUTES FIRE RESISTIVE RATING AND 1-HOUR FRAME.
2. HI/LO DRINKING FOUNTAIN REQUIRED, SUBMIT REVISED PLAN SHOWING THIS REQUIREMENTS.
3. PORTION OF THE COUNTER SHALL BE ADA COMPLIANT.
4. THE PLAN SHOWS THE STOREFRONT GLAZING IS CONNECTED TO A RATED 1-HOUR DEMISING WALL, ANY RATED WALL SHALL BE CONNECTED TO A WALL OR TO A MULLION WITH FIRE SAFING ON BOTH SIDES OF THE WALL. SUBMIT DETAILS AND REVISED PLAN PRIOR TO ISSUANCE OF PERMIT.
5. SAFETY GLAZING AS REQUIRED IN IBC 2406.
6. MEMBRANE PENETRATION INTO THE 1-HOUR DEMISING WALL SHALL NOT REDUCED THE FIRE RESISTANCE OF THE WALL.