Notes:
ALL WORK PERFORMED MUST MEET THE 2003 IBC STANDARDS.
ALL WOOD USED IN CONSTRUCTION SHALL BE FIRE TREATED.
SUBJECT TO FIELD INSPECTION APPROVAL.
CALL (972) 292-5386 FOR INSPECTION.
PIER INSPECTION REQ'D. PIERS ARE 18" X 6' SEE DETAIL
1. All work subject to field approved inspections and testing.
2. Below grade wasted tie-ins, solvent joint or "mission" type S.S. bands.
3. Below grade piping to be bedded with sand.
4. Trenches to be compacted at backfill.
5. Overhead piping to be hung properly to structure.
6. Floor and hub drains installed with trap primer.
7. No pvc allowed in return air plenums.
8. All connections to existing plumbing shall be accessible at inspection.
9. Water heaters to be installed per IPC 2003 w/local amendments.
10. All soldered joints shall be made with flux conforming to ASTM B813.
11. Bottom fed water heaters shall be installed with vacuum relief valve.
12. Penetrations through fire rated assemblies shall be firestopped by approved method for material.
(6/14/2007 10:11 JM)
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. NO ALUMINIM WIRE PERMITTED.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2003 IBC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2003 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.
4 ACRES, CNEW / TUSCANY MEADOWS PARK