Notes:
3906 AC, 4710 SF, SFR / 2 STORY
6/25/2007 12:00:00 AM
01. ENERGY STAR / GREEN BUILDING.
02. COMPLIANCE WITH THE 2003 CODES, AMENDMENTS, ORDINANCES & SUBDIVISION REQUIREMENTS.
03. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
12. BEAMS=10"W X 30"D.
25. TEMPERED GLASS REQ'D AT WINDOWS WITHIN 2' OF DOOR OPENINGS.
29. TEMPERED GLASS AT FLOAT GLASS WINDOWS GREATER THAN 9 SQ FT, LESS THAN 18" OFF FINISH FLOOR, WITHIN 3'-0" OF A WALKING SURFACE.
37. DRIVEWAY SLOPE MUST NOT EXCEED 12% - PLOT PLANS W/GRADES REQUIRED.
39. MAX OF 24 SQ FT OF 6" GLASS BLOCK ALLOWED IN 1 HOUR FIRE RATED WALL ASSEMBLY.
40. ON "0" SET-BACK SIDE OF HOUSE NO METERS OR VENTS ARE ALLOWED. GUTTER DOWNSPOUTS MUST DISCHARGE ONTO SAME PROPERTY 5'-0" FROM FOUNDATION.
42. THIS SUBDIVISION MAY REQUIRE H.O.A. DESIGN APPROVAL PRIOR TO PLAN SUBMITTAL AND CONSTRUCTION.
46. FRONT ENTRY CURB CUT PER ENCLOSED DESIGN SKETCH.
49. INSPECTIONS, TESTING, COMPONENT VERIFICATION AND FINAL HERS SCORE BY THE THIRD PARTY RATER PROVIDING THE REM-RATE REPORT.
50. ET BASED CONTROLLER REQUIRED FOR AUTOMATIC IRRIGATION SYSTEMS PER CITY ORDINANCE ZA06-0005 DATED 11/24/2006.
54. PROVIDE EXPANSION JOINTS IN MASONARY FACADE.
2nd FLOOR: 2-BED ROOMS, 2-BATHS, GAME ROOM AND ATTIC ACCESS ONLY.
THREE OR MORE RISERS REQUIRE A HAND RAIL.
STUCCO 1 HR. FIREWALL-3/8" THICK CEMENT PLASTER ON EXPANDED METAL LATHE OVER 1/2" EXTERIOR GYP.BOARD AND 5/8" INTERIOR WALL SHEET ROCK EQUAL TO UL-U356.
56. LETTERS OF ACCEPTANCE REQUIRED FROM BOTH ENGINEERS FOR CO.
NO PATIO COVER OR ACCESSORY STRUCTURE MAY EXTEND OVER THE
2nd FLOOR: 2-BED ROOMS, 2-BATHS, GAME ROOM AND OPTIONAL MEDIA.