Notes:
3040 SQ FT, CIFO / LEGACY HOME
7/21/2007 12:00:00 AM
1. VB construction--any wood used shall be fire treated/retardant.
2. fully sprinkled bldg.
3. mop sink req'd. IPC 2003
4. hi/lo drinking fountain req'd. IPC 2003
5. 1016.3 IRC 2003 dead end corridor not permitted, 21' shown on plans
see amendments deleting exception #2.
6. Interior finishes: flame spread 26-75 smoke developed 0-450.
7. UL U-465 demising walls 1 hr. fire/smoke construction floor to deck, fire caulk floor to deck.
8. T. 160.1 IRC 2003 with 69 occupants 2 exits req'd. the corridor shall be 1 hr. fire/smoke construction with 1 hr door assembly fire/smoke proof between showroom and office space. see plans for direction of door swings. F/S dampers are req'd. where duct through penetration are present at corridor.