Notes:
4035 SQ FT, CIFO / GLOBAL RESOURCES
8/30/2007 12:00:00 AM
1. SUBJECT TO FIRE MARSHAL APPROVAL FIELD APP'D. INSPECTIONS & TESTING SHALL APPLY.
2. STRUCTURAL BUILDING ELEMENTS INVOLVING WOOD PRODUCTS SHALL BE FIRE TREATED.
3. FULLY SPRINKLED.
4. INTERIOR FINISHES: CLASS C FLAME SPREAD 76--200 SMOKE DEVELOPED 0--450.
5. RATED GLAZING @ ENTRY DOOR 20 MIN. IBC 03' 715.3.3 SEE DETAIL.
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. NO ALUMINIM WIRE PERMITTED.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2003 IBC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2003 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.
Mechanical ordinance 06-11-113
1. All duct work to be sealed with mastic, welds, or gaskets; Tapes not accepted.
2. All exhaust fans to terminate outside of the bldg.
3. Fresh air intakes to be 10 ft. away or 2 ft. below exhaust gas openings & require dampers to close intake when not in use.
4. Mech. Contractor to be responsible for duct sizing and load calculation.
5. Mech. Contractor to verify fresh air intake per IMC 403 & table 403.3
6. Mech. Installation to comply with 2003 IECC and supplements.
7. Rigid duct required with 6 ft. (R-6) flex duct connector allowed between rigid duct and diffuser.
8. Set back T-Stats required for each zone.
9. Smoke detectors/dampers to be installed per chapter 6 of IMC.
10. Subject to field review and inspection
11. FIRE/SMOKE DAMPERS WHERE PENETRATING 1 HR. CORRIDORS WHERE THESE DUCTS COMMUNICATE WITH OTHER OPENINGS IN THAT SAME CORRIDOR.