Notes:
175 SQ FT, SALT / ENCLOSE 3RD CAR TANDEM GARAGE
3/27/2008 12:00:00 AM
01. ENERGY STAR / GREEN BUILDING.
02. COMPLIANCE WITH THE 2006 CODES, AMENDMENTS, ORDINANCES & SUBDIVISION REQUIREMENTS.
03. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
23. GARAGE MUST BE A MIN. 18'W X 20'D CLEAR SHEET ROCK TO SHEET ROCK.
44. CO DETECTORS REQ'D ON ELECT LEGEND & ELECT PLAN 1/1000 SQ FT & 1 PER FLOOR MIN.
49. GREEN BUILDING VENTILATION REQUIREMENT BASED ON ASHARAE 62.2 STANDARD.
55. FUEL BURNING HOT WATER HEATER INSTALLATION MUST BE CODE COMPLIANT.
need mech. contractor for supply air extension to new bdrm.
remove sheetrock at garage wall and install insulation per Energy Star Report, at new wall insulation req'ments per Energy Star Report.
5/8" type x gyp. bd. on new wall garage side.
new wall install treated sill plate and shoot plate with nails and washers ea. 33"
seal sill plates at garage flr.
maintain correct clearances at electrical panel 110-26 NEC 2005.
w/h's to be moved to attic with compliant platform, ensure 300 # ladder access.
per green bldg. ordinance fresh air must be provided to each bdrm. by hvac unit.