Notes:
200 SQ FT, SADD / ROOM ADDITION
1/13/2009 12:00:00 AM
002. COMPLIANCE WITH THE 2006 CODES, AMENDMENTS, ORDINANCES & SUBDIVISION REQUIREMENTS.
003. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
023. GARAGE MUST BE A MIN. 18'W X 20'D CLEAR SHEET ROCK TO SHEET ROCK.
025. TEMPERED GLASS REQ'D AT WINDOWS WITHIN 2' OF DOOR OPENINGS.
031. SIDING DIRECTLY OVER MASONRY AT SECOND STORY IS NOT ALLOWED.
033. MEDIA ROOM WITH CLOTHING STORAGE MUST HAVE A CODE COMPLIANT EGRESS WINDOW.
034. SIDING & TRIM MUST BE CEMENT FIBER OR ENGINEERED TREATED WOOD PRODUCT IF APPLICABLE.
044. CO DETECTORS REQ'D ON ELECT LEGEND & ELECT PLAN 1/1000 SQ FT & 1 PER FLOOR MIN.
058. 2006 IECC COMPLIANCE REQUIRED.
ALL PENETRATIONS AND BOTTOM SILL PLATE SHALL BE SEALED WITH FOAM.
LITE IN CLOSET SHALL BE 12" HORIZONTAL FROM ANY SHELF, VERTICALLY FLOOR TO CEILING.
ALL OUTLETS IN THIS ROOM SHALL BE ARC-FAULT PROTECTED WITH CARBON MONOXIDE/SMOKE COMBO DETECTOR INSTALLED IN THE ROOM.
5' SQ. FT OF EMERGENCY EGRESS AT WINDOW.