Notes:
708 A/C GAMERM. & 440 SQ. FT PATIO CVR.
4/30/2010 12:00:00 AM
NEW A/C IS 708 SQ. FT.
NEW PATIO COVER IS 440 SQ. FT.
NEW TOTAL UNDER ROOF AREA IS 5465
PLANS DO NOT INDICATE NEW LOCATION OF; OR TYPE OF WATER HEATER TO BE USED. NO ENCROACHMENT OF W/H IN GARAGE ALLOWED.
ENTRY HALLWAY OPENING TO HALLWAY LEADING TO BDRMS. MUST BE 36" WIDE. NO EXCEPTIONS.
HARD WIRED COMBO SMOKE/CARBON MONOXIDE DETECTORS ARE REQ'D. EACH 1000 SQ. FT. AND WITHIN 10' OF GARAGE ENTRY.
FIRST FLOOR SIDING IS NOT ALLOWED AT REAR ELEVATION. STUCCO OR STONE OR BRICK ONLY BASED ON CZO 00-11-01 ART. IV SECT. 9.09
001. ENERGY STAR / GREEN BUILDING.
002. COMPLIANCE WITH THE 2006 CODES, AMENDMENTS, ORDINANCES & SUBDIVISION REQUIREMENTS.
003. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
008. BEAMS=10"W X 24"D.
024. EXITWAYS (HALLWAYS) MUST BE A MIN. 36"W INCLUDING ARCHED OR CASED OPENINGS. (TWO OR MORE ROOMS)
025. TEMPERED GLASS REQ'D AT WINDOWS WITHIN 2' OF DOOR OPENINGS.
026. TEMPERED GLASS REQ'D AT ALL BATHROOM HAZARD LOCATIONS.
029. TEMPERED GLASS AT FLOAT GLASS WINDOWS GREATER THAN 9 SQ FT, LESS THAN 18" OFF FINISH FLOOR, WITHIN 3'-0" OF A WALKING SURFACE.
034. SIDING & TRIM MUST BE CEMENT FIBER OR ENGINEERED TREATED WOOD PRODUCT.
035. 2 X 6 PLUMBING (VENT STACK/WASTE) WALLS REQ'D AT ALL FIXTURES.
044. CO DETECTORS REQ'D ON ELECTRICAL LEGEND & ELECTRICAL PLAN 1/1000 SQ. FT. & 1 PER FLOOR MINIMUM WITH (1) ON THE AC SIDE OF THE GARAGE DOOR.
049. GREEN BUILDING VENTILATION REQUIREMENT BASED ON ASHARAE 62.2 STANDARD.
054. PROVIDE EXPANSION JOINTS IN MASONARY FACADE.
055. FUEL BURNING HOT WATER HEATER INSTALLATION MUST BE CODE COMPLIANT.
058. 2006 IECC & ENERGY STAR COMPLIANCE REQUIRED.