Notes:
ADD ELECTIC POWER FOR (IT) ROOM
3/11/2011 12:00:00 AM
Electrical Ordinance 08-01-10
THESE ARE GENERAL NOTES; ITEMS CAN BE VERIFIED IN THE FIELD.
PRIMARY AND SECONDARY PROTECTION IS REQ'D. ON TRANSFORMERS, TAP RULES WILL APPLY.
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
LIGHTING COMCHECK COMPUTATIONS MUST MATCH PLANS.
002. ONLY ALUMINIM WIRE PERMITTED IN SERVICE ENTRANCE AND FEEDERS 1/0 AND LARGER STABIL-ALLOY SERIES 6000 & 8000.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2006 IBC 1011.1 & 2005 NEC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2006 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2005 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE ALONG WITH THE FOLLOWING COMMENTS.
008. ANY WIRE/CONDUCTORS USED IN HVAC PLENUM AREA SHALL BE PLENUM RATED.
010. ALL EXTERIOR LIGHTING SHALL COMPLY WITH COMPREHENSIVE ZONING ORDINANCE ARTICLE IV SECTION 6 LIGHTING & GLARE RQ'MENTS.
011. AN AS-BUILT LEGIBLE PANEL SCHEDULE SHALL BE AFFIXED TO THE INSIDE OF ELECTRICAL PANELS FOR EACH TENANT.
012. BATTERY BACK-UP LIGHTING-----------THIS IS MANDATORY LIGHTING FOR ALL INTERIOR EGRESS/INGRESS POINTS & IN COMMERCIAL RESTROOMS.
013. GROUNDING AND BONDING SHALL COMPLY WITH ARTICLE 250.
BLDG. STRUCTURAL STEEL, GROUND ROD, COPPER DOMESTIC COLD WATER PIPE (UFER IF AVAILABLE PER 250-81)
014. RECOMMENDATION---ARTICLE 110-13 (b) NATURAL COOLING OF EQUIPMENT IS REQ'D. AND SHALL NOT BE OBSTRUCTED. NATURAL VENTILATION MUST COMPLY WITH IMC SECTION 402 AND T.403.1 WITH 0.05 CFM/SQ.FT.
015.PROVIDE 1 HR. RATED ELECTRICAL OUTLET BOXES IN @ I HR. CORRIDOR AND @ DEMISING WALLS.
DOOR AT MECHANICAL/ELECTRICAL ROOM SHALL OPEN OUT IN THE DIRECTION OF EGRESS.
MAINTAIN PROPER WORKING CLEARANCES IN MECHANICAL/ELECTRICAL ROOM ARTICLE 110-26.