Notes:
CALT / VERION FRISCO STORE CELLULAR EQUIPMENT
8/22/2014 12:00:00 AM
1. ALL WORK PERFORMED MUST MEET THE 2006 INTERNATIONAL BUILDING CODE, LOCAL AMENDMENTS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE AND ALL OTHER CITY ORDINANCES.
2. SUBJECT TO FIRE MARSHAL APPROVAL AND INSPECTION.
SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTIONS REQUIRED.
PLANS PROVIDE LIMITED INFORMATION ABOUT INSTALLATION METHODS AND DESIGN FOR ELECTRICAL, PLUMBING AND MECHANICAL SCOPE. PERMIT SHALL BE SUBJECT IN WHOLE TO FIELD INSPECTION AND APPROVAL. PERMIT APPROVAL DOES NOT IMPLY APPROVAL OF INSTALLATION METHODS AND DESIGN BASED ON LIMITED INFORMATION PROVIDED.
1.MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS. LIGHT COMCHECK CALCULATIONS MUST MATCH PLANS.
2. ALUMINUM WIRE PERMITTED IN SERVICE ENTRANCE AND FEEDERS 1/0 AND LARGER STABIL-ALLOY SERIES 6000 & 8000.
3.PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
7. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
8. ALL CONDUCTORS MUST TERMINATE IN DEVICES THAT HAVE BEEN PROPERLY TIGHTENED TO MANUFACTURERS’ TORQUE SPECIFICATIONS USING THE PROPER TORQUE TOOL.
10. LEGIBLE PANEL SCHEDULE SHALL BE PROVIDED AT ALL PANEL LOCATIONS.
11. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2011 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE.
13. GROUNDING AND BONDING SHALL COMPLY WITH ARTICLE 250 2005 NEC. STRUCTURAL STEEL, GROUND ROD, COPPER DOMESTIC SERVICE (UFER IS AVAILABLE PER ARTICLE 250.81).
14. THE GROUNDED CONDUCTOR SMALLER THAN #6 AWG MUST BE WHITE OR GRAY INSULATION NO PHASING WIRES PER NEC ARTICLE 200.7.
15. THE GROUNDING CONDUCTOR SMALLER THAN #6 AWG SHALL BE GREEN INSULATION OR BARE PER NEC ARTICLE 250.119.
***CONDUCTOR DE-RATING REQUIRED. THIS SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR AND MUST BE COORDINATED AND APPROVED BY FIELD INSPECTION.