Notes:
360 SQ FT, SALT / PATIO COVER
11/18/2014 12:00:00 AM
PATIO COVER
142. * ALL WORK PERFORMED MUST MEET THE 2012 IRC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
145. * OUTSIDE OF POST CAN NOT ENCROACH THE REAR YARD SETBACK, UP TO THREE FOOT OVER-HANG IS ALLOWED.
148. ***LAG BOLT MUST PENETRATE MAIN HOUSE STUD MIN 1 ½".
151. ***MAY NOT INTRUDE ON SIDE YARD SETBACKS.
050. DOUBLE UNDERLAYMENT REQUIRED ON COMPOSITION ROOFS WITH A 4:12 PITCH OR LESS
GRILL AREA
142. * ALL WORK PERFORMED MUST MEET THE 2012 IRC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
165. MAY NOT INTRUDE ON SIDE YARD SETBACKS.
143. SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTION.
FIREPLACE
172. * ALL WORK PERFORMED MUST MEET THE 2012 IRC STANDARDS.
175. * FIREPLACE MUST BE 100% MASONRY.
176. * VENTING AND FLUE MUST MEET MANUFACTURERS SPECIFICATIONS.
177. * MUST MAINTAIN TEN FOOT CLEARANCE FROM ALL COMBUSTABLE ITEMS.
178. * CHIMNEY MUST MAINTAIN A MINIMUM OF 2' IN CLEARANCE (EXCLUDING SPARK ARRESTOR) IN HEIGHT WITHIN A 10' RADIUS OF CHIMNEY.
179. * FOOTER THICKNESS 12" MIN & WIDTH 6" EACH SIDE OF FIREPLACE WALL.
**A GASLINE PRESSURE TEST IS REQUIRED WHEN ADDING GAS TO AN OUTDOOR FIREPLACE.**
173. SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTION.
153. CITY OF FRISCO APPROVAL IS NOT IN LIEU OF HOMEOWNER ASSOCIATION (HOA) REQUIREMENTS. REFERENCE HOA BYLAWS FOR SUBDIVISION REQUIREMENTS