Notes:
27 SQ FT, SALT / FIREPLACE
6/14/2016 12:00:00 AM
FIREPLACE
*100% MASONRY STRUCTURE, NO GREATER THAN 8 FT MAY ENCROACH INTO THE REAR YARD UP TO 10 FT FROM PROPERTY LINE.*
** A GASLINE PRESSURE TEST IS REQUIRED WHEN ADDING GAS TO AN OUTDOOR FIREPLACE **
1. ALL WORK PERFORMED MUST MEET THE 2012 IRC STANDARDS.
2. FIREPLACE MUST BE 100% MASONRY.
3. VENTING AND FLUE MUST MEET MANUFACTURERS SPECIFICATIONS.
4. MUST MAINTAIN TEN FOOT CLEARANCE FROM ALL COMBUSTABLE ITEMS.
5. CHIMNEY MUST MAINTAIN A MINIMUM OF 2' IN CLEARANCE (EXCLUDING SPARK ARRESTOR) IN HEIGHT WITHIN A 10' RADIUS OF ROOF.
6. FOOTER THICKNESS 12" MIN & WIDTH 6" EACH SIDE OF FIREPLACE WALL.
7. SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTION.
8. CITY OF FRISCO APPROVAL IS NOT IN LIEU OF HOMEOWNER ASSOCIATION (HOA) REQUIREMENTS. REFERENCE HOA BYLAWS FOR SUBDIVISION REQUIREMENTS.