Notes:
5/29/2018 1:52:11 PM
001. COMPLIANCE WITH THE AMENDED ZONING ORDINANCE (13-06-36) AND ALL DEED RESTRICTIONS SHOWN ON THE FINAL PLAT (DRIVEWAY; FENCE).
002. COMPLIANCE WITH THE 2015 BUILDING CODES, LOCAL AMENDMENTS, PD AND FINAL PLAT REQUIREMENTS.
003. TERMITE BARRIER PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
007. MAX SIDEWALK SLOPE IS 8.3%, ADD STEPS AS REQ'D.
016. BEAMS=10"W X 30"D.
029. PROVIDE EXPANSION JOINTS IN MASONARY FACADE.
033. ALL SIDING,TRIM,SHAKES AND SIMILAR NON-MASONRY EXTERIOR SURFACE COVERINGS MUST BE OF CEMENTITIOUS MATERIAL.
039. BOTH INTERIOR AND EXTERIOR STAIRS OF 4 RISERS OR MORE REQUIRE A HANDRAIL
043. TEMPERED GLASS REQUIRED AT ALL BATHROOM HAZARD LOCATIONS, INCLUDING WINDOWS AND PARTITIONS IF GLAZING IS LESS THAN 60" ABOVE ANY STANDING/WALKING SURFACE.
045. MINIMUM OF 24" ON SILL HEIGHT AT 2ND STORY OPERABLE WINDOWS. EMERGENCY/ESCAPE RESCUE OPENINGS SHALL HAVE NET CLEAR OPENING OF \u003e= 5.7 SQFT. MINIMUM NET CLEAR HEIGHT OF 24" AND NET CLEAR WIDTH OF 20" (GRADE FLOOR OR BELOW \u003e= 5.0SQFT).
046. SECOND STORY WINDOWS (SIZE AND TYPE) MUST INCLUDE HEAD HEIGHT
048. MEDIA ROOM WITH CLOTHING STORAGE MUST HAVE A CODE COMPLIANT EGRESS WINDOW.
058. GREEN BUILDING VENTILATION REQUIREMENT BASED ON ASHARAE 62.2 STANDARD.
059. DRIVEWAY, LEADWALK AND GARAGE DOOR ENHANCEMENTAND TREATMENT PER THE ENCLOSED
061. SEE ENCLOSED SHEET FOR WOOD FENCE CONSTRUCTION AND (OR) ORNAMENTAL IRON AS PER PD REQUIREMENT