Notes:
2/14/2019 10:31:48 AM
Standard Notes:
1- Interior trim; materials, other than foam plastics used as trim shall have preferably class A flame spread (0-25) & smoke-developed index (0-450) per ASTM E-84 or UL 723.
2-Combustible trim, excluding handrails & guardrails, shall not exceed 10 percent of the aggregate wall or ceiling area in which it is located. ( NFPA 701)
3-1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1). Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2). Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits.
Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.Toilet rooms containing two or more water closets or a combination of water closet and urinal.
4-1006.3.1 Illumination level under emergency power. Emergency lighting facilities shall be arranged to provide initial illumination that is at least an average of 1 footcandle (11 lux) and a minimum at any point of 0.1 footcandle (1 lux) measured along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 footcandle (6 lux) average and a minimum at any point of 0.06 footcandle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded.
5- All mechanical equipment (Roof or ground- mounted ) shall be screened from view at a point (6) feet above ground level at the property line. If a parapet does not accomplish this screening, a screening wall equal to the height of the equipment shall be provided. (screening shall be compatible to building materials.)
6-. Demising walls separating tenants shall be rated 1 hr. Fire smoke construction, all penetrations thru demising walls shall be fire caulked floor to roof deck. Rated walls ending at the storefront must provide 1 hr fire/smoke connection to the nearest mullion or pilaster.(Ord. 508.1)
7- Metal stud walls shall not penetrate thru roof decking, lateral bracing required. (do not anchor partitions studs to ceiling grid system. Demising wall studs must be over ceiling height & braced max 4'-0" o/c to structural building framing (above ceiling). Provide gypsum board j trims at bottom & top of walls as required per ASTM C-754 for steel framing with GWB.)
8- Any duct penetrations thru demising walls shall have fire/smoke dampers installed.
9- Where above ceiling area is used as HVAC plenum—all wiring shall be plenum rated.
10- Contractor to verify fire riser room location. There shall be access to the centrally located or individually located fire riser room. Where *RTU’s are applicable there shall be same for access to this equipment. (where installed, roof hatch access shall be fire smoke sealed).
11- Tempered windows/glass where applicable.
12- Millwork to meet TAS requirements.
13- Subject to M.E.P. reviews, fire marshal, field inspections & the federal ADA requirements.
14. All public bath/ rest rooms are required to comply with Accessibility standards IBC (ICC A117.1),& TAS.
15-Hi/lo drinking fountains required.(2902.1 & 1109.5.1).
16-Provide service sink. (IBC 2902.1)
2/14/2019 10:32:13 AM
**APPROVAL OF THIS BUILDING PERMIT IS NOT AN AFFIRMATIVE
DEFENSE TO CURRENT OR FUTURE STATE OR FEDERAL LAWS RELATED
TO CBD OR CANNABIDIOL CONTAINING PRODUCTS.**
2/14/2019 10:32:38 AM
***HI/LO DRINKING FOUNTAIN REQUIRED PER 2902.1 & 1109.5.1
(WATER COOLERS AND/OR BOTTLED WATER DO NOT MEET THIS
REQUIREMENT) INSPECTOR TO VERIFY INSTALLATION ONSITE***